Alarm conditions trigger an event message that displays in the event
log.
Figure 60 shows the temperature and voltage thresholds for each alarm
and how to resolve the problem.
To enable or disable the alarm:
1. From SAM, select Manage EF2800 > General Config > Audio Alarm.
The Audio Alarm page displays.
2. Select the alarm option you want.
3. Click Change Configuration.
Figure 60. Alarm thresholds
Alarm threshold What to do when the alarm sounds
EF2800 internal temperature
Warning: 0°C to 4°C and
66°C to 70°C
Shutdown: <0°C and >70°C
Check SAM to confirm what the
alarm means by clicking Event Log
on any page.
Check the ambient temperature and
lower it, if needed. Ambient
temperature should be less than
40°C.
•Check that the
EF2800 has good
airflow clearance.
SM CPU temperature
Warning: 0°C to 4°C and
91°C to 100°C
Shutdown: <0°C and >100°C
Same as above.